TE-660 Dew point  On-line / Transmitter

TE-660 Dew point  On-line / Transmitter

Description

TE-660 Dew point transmitter with a measuring range down to -60°C dp is ideal for applications in compressed air systems, plastic dryers and industrial drying processes. An integrated auto-calibration procedure permits a measurement accuracy of <2 °Cdp. The measured values for dew point is available on an analog 4-20 mA. Integration into the measurement task is simplified by the compact d

Features
Fully calibrated at TEKHNE factory
Innovated Polymer technology
Measuring range:-60 to +20 ℃ dp
Measuring range:-60 to +20 ℃ dp


  • Fully calibrated at TEKHNE factory
  • Innovated Polymer technology
  • Measuring range:-60 to +20 ̊C dp
  • Accuracy:± 2 ̊C dp (at 25 ̊C)
  • Pressure:up to 8 MPa
  • TE-660 On-line with monitor
         TE-660 Transmitter without monitor
  • Fast response time




Introduction

TE-660 Dew point transmitter with a measuring range down to -60°C dp is ideal for applications in compressed air systems, plastic dryers and industrial drying processes. An integrated auto-calibration procedure permits a measurement accuracy of <2 °Cdp.

The measured values for dew point is available on an analog 4-20 mA. Integration into the measurement task is simplified by the compact design and the exceptionally robust stainless steel housing.

Application


  • Monitoring of compressed air systems


            refrigerant type dryer

            absorption dryer

            plastics dryer


  • Semiconductor
  • Industrial Furnace
  • Battery Predictor



Installing

If installing directly into the process, a stop valve should be at both sides of the installation point. This makes it easy to remove the transmitter for maintenance and calibration.


Monitor for TE-660 On-line

If power supply and display are required, TK-100 On-line monitor is included in TK-660 On-line.


Technical Specifications

TE-660 Transmitter

Measurement range               -60 to 20 °Cdp

Accuracy                                 ±2 °Cdp (at 25 °C)

Response time t90                 < 5 min (-20 °Cdp0-60 °Cdp)

                                                  < 15 sec (-60 °Cdp0-20 °Cdp)

Analog output                        4-20 mA(3-wire technology) RL < 500 Ohm

Resolution of analog output     2 µA

Temperature dependence        ±5ppm of the measuring span / °C  (Deviating from 20 °C)

Power supply                            18 to 28 VDC

Power consumption at 24VDC    <20mA + load current

                                                  with auto calibration: 100 mA + load current

Operating pressure                 Up to 8 MPa

Electrical connection               M12 x1  5-pin plug

Sensor protection                   Stainless steel sintered filter

Temperature/humidity operating range -40 to 70 °C / 0 to 100 %RH

Storage temperature                              -40 to 60 °C

Electromagnetic compatibility                 EN61326-1 EN61326-2-3 Industrial environment

                                                                 FCC Part 15 ICES-003 ClassB


Monitor for TE-660 On-line

Display                               5 digit LED

Measurement Ranges        -60 to 20 °Cdp

Outputs                              4-20 mA

Alarm Relays                       3 relay contact

Operating environment      0 to +50 °C (35 to 85 %RH)

Storage environment         -10 to +70 °C (max 60 %RH)

Power supply                     100 to 240 VAC, 50/60 Hz

Sensor cable                      Cable, screened twisted pair (x2), 7/0.2 type 1, common drain. (Max length 1,000 m)